Display | 4 digit 0.56” 7 segment Red LED display for Temperature 4 digit 0.56” 7 segment Green LED display for Set Point |
Sensor | J,K,R & 3 wire PT100 |
Range | J T/C : 0 to 750°C K T/C : 0 to 1250°C R T/C : 0 to 1700°C PT100: -100.0 to +600.0°C |
Accuracy | ±0.1% of Full Scale ± 1 digit |
Relay Logic | In On/Off mode (P=0), Relay programmable as Heater/Cooler logic PID mode, cycle time of 5sec for SSR and 20sec for Relay 5 Amps/220V AC Relay Contact outputs+10V output for SSR |
Proportional Band | -7.0°C to +3.0°C around set point with 10% per degree cut |
Hysterisis Band | Settable from 0°C to 20.0°C |
Percentage Power | User programmable from 0% to 100% to avoid overshoots and save power |
Offset Band | Settable from -20.0°C to +20.0°C |
Memory | Non-volatile EEPROM to save settings |
Configuration Lock | On rear terminals to prevent tampering with configuration except Set Point |
Supply | 220V AC ± 15% @ 50/60Hz |
Dimensions | Front Fascia: 96mm x 96mm x 135mm.
Cut Out : 91mm x 91mm |
Weight | 800 grams |
Display | : 3½ Digit LED Indication. |
Front Panel Controls | : Single Digit Channel No. Indication(from 0 to7) |
: Auto Manual Mode Selection | |
In Auto Mode Display Rate Programmable(1-9sec) In Manual Mode Channel Advance by Press Switch. | |
Ranges Available | : For RTD PT-100 : 0-199.9°C |
: For J Type Thermocouple : 0- 600°C | |
: For K Type Thermocouple : 0-1200°C | |
: For R Type Thermocouple : 0-1600°C | |
Accuracy | : ±0.5% F.S |
Input Power | : 230V or 110V ± 10% 50/60Hz |
Size | : FRONT FACIA : 96 x 96 mm |
: CUTOUT : 91 x 91 mm |
Display | : 4 Digit 0.56" 7 Segment Red LEDs for Temperature 2 Digit 0.56" 7 Segment Green LEDs for Channel Number |
Number of Channels | : Maximum 16 |
Sensor | : J,K,R T/C or 3 wire PT-100 (common for all channels) |
Range | : J T/C : -50°C to 750°C K T/C : -50°C to 1250°C R T/C : 0 to 1700°C PT100: -100.0 to +600.0°C |
Resolution | : 1°C for thermocouples and 0.1°C for PT100 |
Accuracy | : ±0.1% of F.S. ±1 Digit |
Serial Output | : RS-232 output |
Logging Rate | : Settable in Hours:Mins (00:01 to 23:59 ) RTC controlled with battery backup to save 3000 readings |
Real Time Clock | : Adjustable in Hours:Mins and Month/Date |
Auto/Manual mode | : Toggle between Auto/Manual modes with front panel indication of mode |
Display Rate | : 1 to 99 seconds per channel in Auto Mode |
Memory | : Non-volatile EEPROM for saving settings |
Configuration Locks | : 1. At rear terminals to lock number of channels 2. At rear terminals to lock Clock settings |
Supply | : 220V AC ± 15% at 50/60Hz |
Ambient Temp. | : Maximum 55°C |
Size (Front) | : 96 x 192 mm |
Depth | : 170 mm |
Display | : 3½ Digit LED |
Ranges | : 199.9°C, 600°C, 1200°C or 1600°C |
Accuracy | : ±0.5% |
Signal Input | : TC, RTD, mV or mA |
Size | : 96x96mm, 72x72mm, 96x48mm |
Supply | : 110V AC, 220V AC or 12V DC |
Peak Hold Digital Temperature Indicator 6100P For Molten Metals |
Specification :
Display | 4 digit 0.3” 7 segment Red LED display for Temperature 4 digit 0.3” 7 segment Red LED display for Set Point |
Sensor | J,K,R & 3 wire PT100 |
Range | J T/C : 0 to 750°C
K T/C : 0 to 1250°C
R T/C : 0 to 1700°C
PT100: -100.0 to +600.0°C |
Accuracy | ±0.1% of Full Scale ± 1 digit |
Relay Logic | In On/Off mode (P=0), Relay programmable as Heater/Cooler logic In PID mode, cycle time of 2sec for SSR and 20sec for Relay 5 Amps/220V AC Relay Contact output, +10V output for SSR For Limit-2, On/Off mode with Relay programmable as Heater/Cooler 1Amps/220V AC Relay Contact outputs |
Proportional Band | Settable from 0-200.0 |
Integral Time (I) | Settable from 0-3000secs |
Derivative Time (D) | Settable from 0-3000secs |
Hysterisis Band | Settable from 0°C to 20.0°C (For On/Off mode i.e. P=0) |
Percentage Power | User programmable from 0% to 100% to avoid overshoots and save power |
Offset Band | Settable from -20.0°C to +20.0°C |
Memory | Non-volatile EEPROM to save settings |
Configuration Lock | Open terminals 4&5 to lock selection of Sensor, control logic & SSR/Relay selection |
Supply | 220V AC ± 15% @ 50/60Hz |
Dimensions | 48mm x 48mm x 129mm. (Including rear terminal block) |
Weight | 800 grams |
Features
Specification :
Display | 4 digit 0.56” 7 segment Red LED display for Temperature 4 digit 0.56” 7 segment Green LED display for Set Point |
Sensor | J,K,R & 3 wire PT100 |
Range | J T/C : 0 to 750°C K T/C : 0 to 1250°C R T/C : 0 to 1700°C PT100: -100.0 to +600.0°C |
Accuracy | ±0.1% of Full Scale ± 1 digit |
Relay Logic | Relay programmable as Heater/Cooler logic On/Off or time proportional with 15 sec cycle time for heater logic On/Off for cooler logic 5 Amps/220V AC Relay Contact outputs |
Proportional Band | -7.0°C to +3.0°C around set point with 10% per degree cut |
Hysterisis Band | Settable from 0°C to 20.0°C |
Percentage Power | User programmable from 0% to 100% to avoid overshoots and save power |
Offset Band | Settable from -20.0°C to +20.0°C |
Memory | Non-volatile EEPROM to save settings |
Configuration Lock | Open terminals 4&5 to lock the Sensor type, Relay, logic and Set Limits |
Supply | 220V AC ± 15% @ 50/60Hz |
Dimensions | Front Fascia: 96mm x 96mm x 135mm. Cut Out : 91mm x 91mm |
Weight | 800 grams |
Display | 4 digit 0.56” 7 segment Red LED display for Temperature 4 digit 0.56” 7 segment Red LED display for Set Point |
Sensor | J,K,R & 3 wire PT100 |
Range | J T/C : 0 to 750°C K T/C : 0 to 1250°C R T/C : 0 to 1700°C PT100: -100.0 to +600.0°C |
Accuracy | ±0.1% of Full Scale ± 1 digit |
Relay Logic | In On/Off mode (P=0), Relay programmable as Heater/Cooler logic PID mode, cycle time of 5sec for SSR and 20sec for Relay 5 Amps/220V AC Relay Contact outputs+10V output for SSR |
Proportional Band | Settable from 0-200.0 |
Integral Time (I) | Settable from 0-3000secs |
Derivative Time (D) | Settable from 0-3000secs |
Hysterisis Band | Settable from 0°C to 20.0°C (For On/Off mode i.e. P=0) |
Percentage Power | User programmable from 0% to 100% to avoid overshoots and save power |
Offset Band | Settable from -20.0°C to +20.0°C |
Memory | Non-volatile EEPROM to save settings |
Configuration Lock | Open terminals 4&5 to lock the Sensor type, Relay logic and SSR/Relay selection |
Supply | 220V AC ± 15% @ 50/60Hz |
Dimensions | Front Fascia: 96mm x 96mm x 135mm. Cut Out : 91mm x 91mm |
Weight | 800 grams |
Range | : 0-199.9°C, 0-1200°C, or 0-1600°C |
Display | : 0.3 inch 3½ Digit Red LED |
Accuracy | : ±0.5% F.S. |
Battery | : 4 Nos. Pen Torch Cells |
Thermocouple Input | : via Male/Female Connector |
Probes | : Surface, Immersion & Air |
Display | 4 digit 0.56” 7 segment Red LED display for Temperature 4 digit 0.56” 7 segment Green LED display for Set Point |
Sensor | K thermocouple Temp range : 0 to 1250°C Accuracy : ±0.1% of Full Scale ± 1 digit |
Soak time range | 0-999mins |
Heater Relay | On/Off with 3C hysteresis |
Alarm Logic | On for temp < Set Point-100°C during soak time On for 30 seconds after end of soak time |
Relay Rating | 5 Amps/220V AC Relay Contact outputs |
Memory | Non-volatile EEPROM to save Set Temperature, Time and status |
Supply | 220V AC ± 15% 50/60Hz |
Dimensions | 96mm x 96mm x 135mm |
Weight | 800 grams |
Display | 0.56” Red LED display for Channel Number 0.56” Red LED display for Temperature |
Sensor | J/K/R Thermocouples and 3 wire PT100 sensor user selectable |
Range | J-T/C : 0 to 750°C K-T/C : 0 to 1250 C R-T/C : 0 to 1700°C PT100: -100.0 to +600.0 C |
Resolution | 1°C for thermocouples and 0.1C for PT100 |
Channels | Maximum 8 |
Scanning Rate | User settable from 1-99seconds |
Resolution | 1 C for Temperature |
Digital Offset | User settable individually for each channel |
Logging Rate | 1 second to 99Mins59seconds |
Data Logging | Directly create a .csv file on the Pen Drive (compatible with Excel) giving a tabular format values of Date, Time and selected channels |
Real Time Clock | Adjustable Calendar (Month/Date) and Time (Hrs:Mins) |
Accuracy | ±1 C ± 1 Least Significant Digit for Thermcouples ±0.1 C ± 1 Least Significant Digit for PT100 |
Power Supply | 230V AC ± 15% at 50/60Hz |
Mounting Type | Panel Type |
Front Facia | 96mm x 96mm |